28.12 On-load excitation
Use of the constant unsaturated value of Xd leads to values of Ef higher than those that occur for a practical machine. Thus a cylindrical-rotor generator with Xdu = 2 p.u. and carrying rated load at p.f. 0.85 lagging would have Ef = 2.67 p.u. while a practical machine would saturate at around 1.5 p.u. If It were read from the airgap line for Ef = 2.67 p.u. it would be about 15% low. At leading power factor, for which saturation levels are low, the error would be small. However, a more accurate estimate of the field current If is needed in the design of the excitation system and its cooling, and to determine the open-circuit e.m.f. that would be reached if the automatic voltage regulator failed to limit the excitation ...