Electrical interlocking scheme (when the interrupters are manually operated)
The preferred way to achieve interlocking between more than one source of supplies is through electrical schemes only, wherever possible. They are foolproof and can also be operated remotely. Mechanical schemes are generally for smaller installations where, as a result of smaller ratings or cost considerations, a breaker is not used and that imposes a limitation on adopting an electrical interlocking scheme.
The electrical interlocking should preferably be provided through shunt trip releases. It must have a separate a.c. or d.c. source of control supply, such that the operation of the scheme is independent of the main source of supply. For the same reason, interlocking ...