To meet the requirements of a Category 2 fault situation, the safety relay must have the
following specification:
1. A safety check prior to the system being started up will only allow the system
to continue starting up, should no fault be found. This is done as follows:
(a) Ensure the emergenc y stop circuit is made;
(b) A cross-check circuit, i.e. R3, which checks whether R1 or R2 is held stuck in the
closed position;
(c) By using positive guidance contacts, check whether any of the output contacts
have become welded together. The positive guidance contacts ensure that none of
the normally closed contacts ...