Electrical industries 107
7
N
Hence current carrying capacity of cable, /
z
=
correction factors
30
0.94 x 0.725
= 44 A
.
cable size (from tables) = 6.0 mm
2
7.3 x 29.17 x 15
and volt drop = = 3.2 V (acceptable)
F
1000
(b) as (a) then:
Correction factors:
Ambient temperature only 0.87
Thermal insulation 0.75
/
N
30
.
/
z
=^ = = 34.4 A
0.87 0.87
.
cable size (from tables) = 4.0 mm
2
11 x 2.17 x 15
and volt drop = = 4.8 V (acceptable)
1000
v F
'
These calculations establish that in each case a twin cable can be
selected for its current carrying capacity and voltage drop. However, such
twin cables have a smaller C.P.C. than the phase conducto ...