Appendix II

Electrical Data and Tables

TABLE AP2/1

Stranded Annealed Copper Conductor Size with Electrical resistance

Size(AWG)Diameter of each strandCross-sectional area(in mm2; 7 strands)Resistance in ohm/kmat 20°C(as per EN 50288-7a)Resistance in ohm/kmat 20°C(as per UL 13b)
240.5790.20591.1
220.7290.32757.6
0.90.536.8
200.9190.51735.8
1.110.7525
181.160.8222.8
1.291.018.5
161.461.314.2
1.591.512.3
141.852.18.94
2.012.57.56
122.323.35.63
2.584.04.7

image

a European standard.

b Underwriters Laboratory Inc. (United States).

Multipair Instrumentation Cables: Size, Resistance, and Other Physical Data

TABLE AP2/2

Multicore Stranded Annealed Copper Conductor ...