Appendix H: Additional Solved Examples of Shunt Faults Using MATLAB

EXAMPLE H.1 Solve Example G.1 Given in Appendix G Using MATLAB

Consider the system shown in Figure G.1 and the following data:

Generator G1: 15 kV, 50 MVA, X1 = X2 = 0.10 pu and X0 = 0.05 pu based on its own ratings Synchronous motor M: 15 kV, 20 MVA, X1 = X2 = 0.20 pu and X0 = 0.07 pu based on its own ratingsTransformer T1 : 15/115 kV, 30 MVA, X1 = X2 = X0 = 0.06 pu based on its own ratingsTransformer T2: 115/15 kV, 25 MVA, X1 = X2 = X0 = 0.07 pu based on its own ratingsTransmission line TL23: X1 = X2 = 0.03 pu and X0 = 0.10 pu based on its own ratings

Assume a single line-to-ground ...

Get Modern Power System Analysis, 2nd Edition now with the O’Reilly learning platform.

O’Reilly members experience books, live events, courses curated by job role, and more from O’Reilly and nearly 200 top publishers.