Simplified two-axis generator model:
Table A.1 Transmission Lines
Bus i | Bus j | R, pu | X, pu | B, pu |
01 | 02 | 0.0035 | 0.0411 | 0.6978 |
01 | 30 | 0.0008 | 0.0074 | 0.4800 |
02 | 03 | 0.0013 | 0.0151 | 0.2572 |
02 | 25 | 0.0070 | 0.0086 | 0.1460 |
02 | 53 | 0.0000 | 0.0181 | 0.0000 |
03 | 04 | 0.0013 | 0.0213 | 0.2214 |
03 | 18 | 0.0011 | 0.0133 | 0.2138 |
04 | 05 | 0.0008 | 0.0128 | 0.1342 |
04 | 14 | 0.0008 | 0.0129 | 0.1382 |
05 | 06 | 0.0002 | 0.0026 | 0.0434 |
05 | 08 | 0.0008 | 0.0112 | 0.1476 |
06 | 07 | 0.0006 | 0.0092 | 0.1130 |
06 | 11 | 0.0007 | 0.0082 | 0.1389 |
06 | 54 | 0.0000 | 0.0250 | 0.0000 |
07 | 08 | 0.0004 | 0.0046 | 0.0780 |
08 | 09 | 0.0023 | 0.0363 | 0.3804 |
09 | 30 | 0.0019 | 0.0183 | 0.2900 |
10 | 11 | 0.0004 | 0.0043 | 0.0729 |
10 | 13 | 0.0004 | 0.0043 | 0.0729 |
10 | 55 | 0.0000 | 0.0200 | 0.0000 |
12 | 11 | 0.0016 | 0.0435 | 0.0000 |
12 | 13 | 0.0016 | 0.0435 | 0.0000 |
13 | 14 | 0.0009 | 0.0101 | 0.1723 |
14 | 15 | 0.0018 | 0.0217 | 0.3660 |
15 | 16 | 0.0009 | 0.0094 | 0.1710 |
16 | 17 | 0.0007 | 0.0089 | 0.1342 |
16 | 19 | 0.0016 | 0.0195 | 0.3040 |
16 | 21 | 0.0008 | 0.0135 | 0.2548 |
16 | 24 | 0.0003 | 0.0059 | 0.0680 |
17 | 18 | 0.0007 | 0.0082 | 0.1319 |
17 | 27 | 0.0013 | 0.0173 | 0.3216 |
19 | 20 | 0.0007 | 0.0138 | 0.0000 ... |