240 Electric Motors and Drives
with the speed, as shown in Figure 7.5. This region is therefore
known as the 'constant power' region. There is of course a close
parallel with the d.c. drive here, both systems operating with
reduced or weak field in the constant power region. The region
of constant power normally extends to somewhere around
twice base speed, and the motor is allowed to operate with
higher slips than below base speed. The rotor currents are not
excessive, however, because the flux is reduced.
At the upper limit of the constant power region, the current
limit coincides with the pull-out torque limit. Operation at still
higher