In the previous sections the focus was on the modeling of overhead transmission lines. The models that are developed and tabulated in Table E.1 are equally valid for underground cables. One should, however, bear in mind that the capacitance of an underground cable is much higher than it is for an overhead transmission line (see also Section 3.8.2 (Underground Cables) and Table 3.2, for example). Therefore the use of the short line model to represent a short underground cable, thereby neglecting the influence of the capacitance, is not recommended.