Appendix C
Resonant Controller
C.1 Introduction
The resonant controller can be obtained either by applying the internal model principle or by using the coordinate transformation. The two methods are briefly described in the following.
C.2 Internal Model Principle
The internal model principle states that if the models of the reference and of the disturbance are included in the feedback control loop a good reference tracking and a good disturbance rejection capability is ensured. If the goal is to track and reject periodic signals that can be decomposed into sinusoidal components (harmonics), this procedure results in the design of controllers that have a pair of poles on the imaginary axis at the frequencies of the harmonics to track and/or to reject. In fact, the Laplace transform of a sinusoidal signal as the normalized grid voltage, i.e. a disturbance in the current control loop as shown in Figure C.1, is
The transfer function (C.1) will be used to demonstrate the effectiveness of a resonant controller tuned on the fundamental frequency to null the error due to the grid voltage.
Figure C.1 The current control loop of an inverter: Gc (s) is the controller, Gd (s) is the delay of PWM and of the computational device and Gf (s) models the filter and the grid

Considering the ...