9
Grid Converter Control for WTS
9.1 Introduction
This chapter discusses the control issues related to the use of a voltage source converter in wind turbine (WT) systems. Before going into detail on the control of the converter, its model is presented. Then different control structures are discussed. In all of them directly or indirectly the two main issues are the control of the DC link voltage (if there is not a DC/DC converter in charge of it) and the control of the AC power. The AC power can be controlled with the aim either of feeding the main grid or of feeding stand-alone loads or a micro-grid. In the first case the WT system may also offer support to the grid. Once the operation of the grid converter is decided and the strategy to select the reference power is also selected, the power control results, using instantaneous power theory (outlined in Appendix B) in a current and/or voltage control (as shown in Figure 9.1). In fact, the converter can be operated as a controlled current source (typically adopted if the converter is grid connected and does not offer any support to the grid) or as a controlled voltage source (typically adopted if the converter is in stand-alone, micro-grid or grid-supporting mode). In the second case, if an LC filter is also employed the current is controlled (see Figure 9.2). The control of currents and voltages can be done in state variables or in a cascade structure. In the case of operation in a micro-grid and in a grid-supporting mode the ...