128 Installation of conduit systems
Fig.
8.14. A serrated conduit coupling for use with a smooth-bore brass bush {Walsall
Conduits)
of branches. A PVC junction box, for example, breaks continuity, and it is
much easier to use a metal box than to connect effectively the conduits
feeding a PVC box.
Where connections are made to boxes that have enamelled finishes, for
example, the enamel must be removed at the point of conduit entry. The
serrated conduit coupling shown in Fig. 8.14 will greatly assist in main-
taining good continuity at switch-boxes, etc.
Where conduits are terminated in switchfuses or metalclad consumer units
an earth termina