170 Inspection and testing
until the faulty circuit is found. Further tests should then be made on this
circuit to locate the faulty section or equipment.
An aid to testers
When conducting insulation tests, a diagram of connections made at the
commencement of the test is an aid to testers who are not continually engaged
on testing such schemes. A note of each reading should be taken, for it should
be remembered that the fault may not be concentrated on one particular lead,
but may be spread over the system generally, due, for instance, to dampness
which may cause leaks to occur at many points. Under such conditions, the
only way to determin ...