158 Safe and efficient earthing
The neutral conductor is usually connected by the electricity board to earth
electrodes at a number of points along the route (hence the name PME),
particularly when the supply is overhead, and this ensures that the neutral is
earthed even if a break occurs along the route; this factor does not however
directly concern the consumer.
The great advantage of PME is that a metallic path of very low impedance
is provided back to the transformer neutral point, and this means that the
consumer's overload protective devices will normally operate when a phase
to earth fault occurs. Another big advantage is that this pat ...