Earthing
present,
10.0
mm
2
. For example, most new domestic install-
ations now have a
16.00
mm
2
earthing conductor, so all main
bonding will be in 10.0mm
2
. Supplementary bonding conduc-
tors are subject to a minimum of 2.5 mm
2
if mechanically
protected or 4.0 mm
2
if not. However, if these bonding conduc-
tors are connected to exposed conductive parts, they must be
the same size as the CPC connected to the exposed conductive
part, once again subject to the minimum sizes mentioned. It is
sometimes difficult to protect a bonding conductor mechani-
cally throughout its length, and especially at terminations, so it
is perhaps better to use 4.0 mm
2
a ...