All of these foregoing requirements ensure that conductor insu-
lation
is
undamaged when
an
overload occurs.
Under short-circuit conditions
it is
the conductor itself that
is
susceptible to damage and must be protected. Figure
17
shows one
half-cycle of short-circuit current
if
there were no protection. The
RMS value (0.7071 x maximum value)
is
called
the
prospective
short-circuit current. The cut-off point
is
where
the
short-circuit
current
is
interrupted
and an arc is
formed;
the
time
t
x
taken
to
reach this point is called the pre-arcing
time.
After the current has
been
cut off, it
falls
to
zero
as the arc is
being extinguished
Become an O’Reilly member and get unlimited access to this title plus top books and audiobooks from O’Reilly and nearly 200 top publishers, thousands of courses curated by job role, 150+ live events each month, and much more.
O’Reilly covers everything we've got, with content to help us build a world-class technology community, upgrade the capabilities and competencies of our teams, and improve overall team performance as well as their engagement.
Julian F.
Head of Cybersecurity
I wanted to learn C and C++, but it didn't click for me until I picked up an O'Reilly book. When I went on the O’Reilly platform, I was astonished to find all the books there, plus live events and sandboxes so you could play around with the technology.
Addison B.
Field Engineer
I’ve been on the O’Reilly platform for more than eight years. I use a couple of learning platforms, but I'm on O'Reilly more than anybody else. When you're there, you start learning. I'm never disappointed.
Amir M.
Data Platform Tech Lead
I'm always learning. So when I got on to O'Reilly, I was like a kid in a candy store. There are playlists. There are answers. There's on-demand training. It's worth its weight in gold, in terms of what it allows me to do.