288 Power System Transients
Solution 2
(a) Cross-Bonded Cable
Zero-Sequence Positive-Sequence
Amplitude (A) Angle (deg.) Amplitude (A) Angle (deg.)
EMTP simulation 133.8 –21.42 356.4 –86.35
Proposed formulas,
Equations 3.8/3.14
124.1 –21.23 356.7 –86.79
(b) Solidly Bonded Cable
Zero-Sequence Positive-Sequence
Amplitude (A) Angle (deg.) Amplitude (A) Angle (deg.)
EMTP simulation 121.6 –21.80 694.9 –50.40
Proposed formulas,
Equations 3.19,
3.20/3.26
124.8 –22.50 722.7 –49.08
References
1. Ametani, A. 1980. A general formulation of impedance and admittance of
cables. IEEE Trans. Power Appar. Syst. PAS-99(3):902–910.