392 Power System Transients
6.2 Disturbances in Power Stations and Substations
6.2.1 Statistical Data of Disturbances
6.2.1.1 Overall Data
In total, 330 cases of disturbances occurred in substations and generator
stations over the course of 10 years, beginning in 1990 [1]. Table 6.1 classi-
es the disturbances by (a) troubled equipment and (b) causes. As shown
in Table6.1a, one-third of the disturbances affected protection equipment, a
quarter affected telecontrol equipment, and another quarter affected control
equipment. Table 6.1b shows that two-thirds of the disturbances were caused
by LSs, one-sixth by SSs in the main circuits (high-voltag ...