189Transients on Overhead Lines
TABLE 2.6
Maximum Voltages for the No-BFO Case
Line Model
Frequency-Dependent
Line Model
Constant Frequency
Line Model
(kV) (μs) (kV) (μs)
Node 1
Tower top 13,217 0.68 13,026 0.67
Upper arm 12,260 0.67 12,128 0.67
Middle arm 10,348 0.61 10,258 0.61
Lower arm 8,110 0.55 8,058 0.55
Upper horn 7,180 0.66 7,301 0.67
Middle horn 6,796 0.60 6,958 0.61
Lower horn 5,692 0.55 5,901 0.55
Upper phase 5,081 0.67 4,830 0.66
Middle phase 3,682 0.67 3,392 0.67
Lower phase 2,652 0.67 2,313 0.67
Node 2 (substation)
Upper phase 433 2.42 433 2.42
(First peak) 241 0.70 241 0.70
Middle phase 332 15.5 335 15.4
(First peak) 95 0.70 94 0.70
Lower phase 261 ...