In Step 2, shunt reactors are tripped before the line breakers of healthy
phases. It is necessary to trip the shunt reactors of only healthy phases. At
this time, it is not necessary or recommended to trip shunt reactors of the
faulted phase since the current through shunt reactor breakers of the faulted
phase does not cross the zero point.
It is recommended to trip at least half of the shunt reactors of healthy
phases as shown in Figure 3.25 as the tripping will normally lower the com-
pensation rate below 50%. The remaining shunt reactors will be useful in
maintaining the charging current within the leading curre
Become an O’Reilly member and get unlimited access to this title plus top books and audiobooks from O’Reilly and nearly 200 top publishers, thousands of courses curated by job role, 150+ live events each month, and much more.
O’Reilly covers everything we've got, with content to help us build a world-class technology community, upgrade the capabilities and competencies of our teams, and improve overall team performance as well as their engagement.
Julian F.
Head of Cybersecurity
I wanted to learn C and C++, but it didn't click for me until I picked up an O'Reilly book. When I went on the O’Reilly platform, I was astonished to find all the books there, plus live events and sandboxes so you could play around with the technology.
Addison B.
Field Engineer
I’ve been on the O’Reilly platform for more than eight years. I use a couple of learning platforms, but I'm on O'Reilly more than anybody else. When you're there, you start learning. I'm never disappointed.
Amir M.
Data Platform Tech Lead
I'm always learning. So when I got on to O'Reilly, I was like a kid in a candy store. There are playlists. There are answers. There's on-demand training. It's worth its weight in gold, in terms of what it allows me to do.