436 Power System Transients
6.4.2 F-Parameter Formulation for Induced Voltages and Currents
6.4.2.1 Formulation of F-Parameter
Two basic approaches exist to handle electromagnetic induction from a
power line (the inducing circuit) to a pipeline (the induced circuit) [35,36,40–
45]. The rst approach represents the inducing and induced circuits as a mul-
tiphase line system. The alternative method considers the induction from
the inducing circuit as a voltage source [35,37] or as a current source [61] so
that the system becomes a single-phase circuit source approach. As noted in
Reference 46, a multiphase line approach becomes too complicated; one ...