490 Power System Transients
between the grounding electrode and the isolated conductor system and,
because of this, the grounding electrode shows a traits of a nonuniform con-
ductor [26].
7.4.1.5.4 Reciprocity between the Electrodes
Figure 7.22 shows the simulation results of induced voltage V
2
for two dif-
ferent electrodes lengths, that is, x
1
= 5 m and x
2
= 1 m (Cases 311–314) with
y = 1–10 m, together with Cases 131–134 (x
1
= 1 m, x
2
= 5 m). It is clear that the
voltages of the inducing and induced electrodes are the same for the differ-
ent electrode lengths, that is, there exists reciprocity between the electrodes,
just as with an insulated ...