170 Power System Transients
at the middle, and Figure 2.30b at the 1/4 length from the sending end. In
Figure 2.30b, the highest overvoltage of 1.53 pu occurs at the fault point and
its symmetrical position to the center of the line, and the overvoltage distri-
bution is at within the two points. In Figure 2.30a, the highest overvoltage
of 1.56 pu occurs at the center, and the overvoltage decreases rapidly toward
both ends of the line. This observation demonstrates that the region of the
line where the overvoltage is higher than a certain level is wider in the case
of the fault occurring at a point apart from the line center, while the highest ...