441Quality of Power
Solution:
Recall that the total effective rms value is the root-sum-squared (rss) value of the
(fundamental + harmonics), that is,
I IIII
T
th= ++++
1
2
3
2
5
2
7
2
25.... .
The table above gives the actual harmonic current ratios, from which we obtain
using Equation 16.12:
THD
i
=++++++0 173 0 108 0 041 0 032 0 021 0 015
222222
......00 011 0 009
0 212 21 2
..%.
+
= pu or
Similar calculations with theoretical values of I
h
= I
1
/h would give THD
i
= 28.7%,
which is significantly higher than the actual THD
i
found in practical converters.
As seen earlier, the harmonic current I
h
drawn by any nonlinear load on the bus
causes the harmonic distor