81AC Generator
Example 3.10
The no-load frequency of two ac generators is the same, 60.5 Hz. The FDR of
generator-1 is 0.0006 Hz/kW, and that of generator-2 is 0.0008 Hz/kW. If the two
generators are in parallel supplying a total load of 1500 kW, determine the load
shared by each generator and the operating frequency of the bus.
Solution:
Denoting kilowatt power P
1
and P
2
shared by generator-1 and generator-2, respec-
tively, we write the two generator frequency droop line equations as
f
1
= 60.5 – 0.0006 P
1
and f
2
= 60.5 – 0.0008 P
2
.
In parallel operation, f
1
= f
2
= f
bus
and P
1
+ P
2
= 1500 kW. Therefore, we write
f
bus
= 60.5 – 0.0006 P
1
= 60.5 – 0.0008 (1500 – P
1
), which gives P
1
= 857 kW and
P
2
= 1500 – 857 = 643 kW.
The bus frequency is then