241System Protection
the net current difference in two wires going through the eye of the CT sensor. Under
healthy operation, the lead and return currents are equal, and the sensor output is
zero. A short in one line conductor to ground even via a soft fault (high-impedance
fault) results in higher-than-rated current in the lead wire with no change in the
return current. The net unbalance current is picked up by the sensor, which is usually
very small due to a high CT turn ratio. It is, therefore, amplied and then sent to the
actuator coil of electromagnetic relay to open the circuit breaker.
The NEC requires that all 120-V single-phase outlets ...