
215Fault Current Analysis
Solution:
From the infinite main bus to the fault, with all cable impedances negligible, the only
impedance is that of the transformer, which is 5%. Therefore, the bus contribution
to the fault current I
fault.bus
= 100% ÷ 5% = 20 pu (note that this is pu, not percent).
The rated current on the transformer secondary side = 2,000,000 ÷ √3 × 480 =
2406 A/ph. This and all currents below are symmetrical rms values.
Therefore, CB4 current = generator contributions through 2-MVA transformer
secondary
= 20 × 2406 = 48,120 A.
motorrated current =
W500 746
3 460 092090
5
×
×××
=
..
665A
.
Using multiple M = 3 for a 460-V motor as per Section ...