236 Introduction to Electrical Power and Power Electronics
higher voltage at a proportionally reduced current within its own K-factor (not to be con-
fused with the transformer K-rating). For example, if the line voltage is higher by a factor
of K ≤ 1.3, then these two kiloampere ratings must be lowered by a factor of 1/K.
9.4.2 CirCUit Breaker seleCtion
The circuit breaker has several ratings to select, such as
• Rated continuous current it carries within allowable temperature rise
• Rated line voltage it supports with adequate insulation to ground
TABLE 9.3
Typically Standard Circuit Breaker Specification for <2 kV Lines
Continuous Current Rating ...