76 Introduction to Electrical Power and Power Electronics
will accelerate under the prime mover input power, accelerating to increase the rotor
angle to δ
2
. If the fault is cleared in time and the circuit breaker is closed under the
automatic reclosure scheme (common on most systems), the generator starts deliver-
ing electrical power in excess of the prime mover input and starts decelerating to its
original power angle δ
1
after the inertial overshoot to δ
3
. The transient swing will
be such that the accelerating area A
a
is equal to the decelerating angle A
d
. The maxi-
mum allowable fault clearing time for stability can be determined by applyi