148 Introduction to Electrical Power and Power Electronics
n : 1
460 V
1
2
120 V
6 Ω
Load
10. A 2-MVA, 4160/480-V transformer has series impedance of R = 2% and
X= 6%. Determine the (1) full-load voltage regulation of the transformer
at 0.85pf lagging and (2) secondary output voltage on unloading the trans-
former completely.
11. A three-phase, 500-kVA, 4160/480-V transformer bank has R = 1.0% and
X= 5%. Using Equation 2.15 or 2.18 with pu values, determine the % volt-
age rise in the secondary voltage on unloading from the following load
conditions: (1) 80% load at the unity power factor, (2) full load at 0.85 power
factor lagging, and ...